EasyManua.ls Logo

Riello MST 40 - UPS Configuration and Settings Guide

Riello MST 40
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
C
ONFIGURING THE
UPS
The following table shows all possible configurations available to tailor the UPS to your needs in the best way possible.
CP
(Control Panel) = Indicates that the configuration can be edited not only by the configuration software but also using the
control panel (if function editing is enabled on the panel).
SW
(Software) = Indicates that the configuration can be changed from the configuration software only.
FUNCTION DESCRIPTION DEFAULT POSSIBLE CONFIGURATIONS MOD.
Output frequency
Selecting the rated output
frequency
(for the setting to be
active, turn the UPS off
then back on)
50 Hz
50 Hz
60 Hz
CP
Output Voltage
Selects nominal
Output voltage
(Phase / Neutral)
230V
200V *
208V *
220V
230V
240V
CP
220 ÷ 240 in steps of 1V
SW
Operating Mode
Selects one of the 5
operating modes
ON LINE
ON LINE
ECO
SMART ACTIVE
STAND-BY OFF
CP
FREQUENCY CONVERTER
SW
Power off due to
minimum load
Automatically switches off
the UPS in battery
operation when the load
is less than 5%
Disabled
Enabled
Disabled
CP
Autonomy
limitation
Sets the maximum time of
battery operation
Disabled
Disabled (complete battery
discharge)
1 ÷ 65000 in steps of 1 sec.
SW
Low battery
pre-alarm
Sets the estimated
autonomy time left for low
battery warning
3 min.
1 ÷ 255 in steps of 1 min.
(1 to 7 min from the panel)
SW
Battery test
Sets the interval of time
for the automatic
battery test
40 hours
Disabled/Enabled (from the panel)
1 ÷ 1000 in steps of 1 hour
SW
Maximum load
alarm threshold
Selects the user
overload limit
Disabled
Disabled
0 ÷ 103 in steps of 1%
SW
Sound alarm
Selects the operating
mode of the sound
alarm
Reduced
Normal
Reduced: does not sound because
of momentary intervention
of the bypass
CP
Auxiliary socket
(power share)
Selects the operating
mode of the auxiliary
socket
Always
connected
Always connected
Disconnected after n seconds of
battery operation
Disconnected after n seconds from
the end-of-discharge alarm signal
... (see configuration software
manual)
SW
Battery expansion
Sets the Ah installed
(external battery
extension)
0 Ah
Min.: 0 - Max.: 999
(in steps of 1 Ah)
CP
Language**
Selects the
display language
English
English
Italian
German
French
Spanish
Polish
Russian
Chinese
CP
Date and time
Sets the date and time -- --
CP

Table of Contents

Related product manuals