    Manuel BonillaSep 23, 2025
    What does it mean if my Riello UPS displays codes L01, L10, L38, L39, L40, or L41?
    • J
      Joshua MartinezSep 23, 2025
      This can be caused by a fault in the temperature probe, UPS cooling system, main auxiliary power supply, or static bypass switch. Activate the maintenance bypass (SWMB), turn the UPS off and then on again. Exclude the maintenance bypass. If the problem persists, call your local service centre.
  • T
    Todd PollardAug 23, 2025
    What to do if my Riello UPS displays codes A22, A23, A24, F23, L23, L24, or L25?
    • D
      Daniel MooreAug 25, 2025
      This can happen if the load applied to the Riello UPS is too high. Reduce the load to below the 100% threshold, or the user threshold if the codes A22, A23, or A24 are displayed.
  • S
    Samantha RoachAug 25, 2025
    What does it mean when my Riello MCT 10 display shows codes L26, L27, or L28?
    • P
      Paul HuynhAug 26, 2025
      This indicates a short circuit at the output of the Riello UPS. To resolve this: 1. Power off the UPS. 2. Disconnect all devices connected to the affected phase. 3. Power the UPS on again. 4. Reconnect the devices one by one to identify the faulty device.
  • R
    Richard LewisAug 27, 2025
    What does the S06 code on my Riello MCT 10 display mean?
    • Y
      ycoxAug 27, 2025
      This issue occurs because of discharged batteries. You should wait for the batteries to recharge, or you can force power on from the System On menu.
  • N
    nguyencharlotteAug 27, 2025
    Why is my Riello UPS running on battery when mains voltage is present?
    • B
      Brian CummingsAug 27, 2025
      The Riello UPS might be running on battery power due to a protective device upstream being activated. Reset the protective device, but first check for any overload or short circuit at the UPS output. Another cause may be that the input voltage is outside tolerance limits for mains operation. In this case, wait for the input mains voltage to return within the tolerance limits for the UPS to return automatically to mains operation.
  • M
    Mason EverettSep 16, 2025
    What to do if my Riello UPS displays codes A26 or A27?
    • C
      cartertaraSep 16, 2025
      This can happen if the battery fuses are blown or the fuse holder isolators are open. Replace the fuses or close the isolators (SWBATT). If necessary, replace fuses with others of the same type.
  • K
    Kayla CamachoSep 14, 2025
    What does it mean when my Riello MCT 10 display shows codes F42, F43, F44, L42, L43, or L44?
    • C
      Chelsea MullinsSep 14, 2025
      This can happen if the internal protection fuses on the batteries have blown. Call the nearest service centre.
  • P
    Paul ThompsonSep 15, 2025
    What does it mean if my Riello UPS displays codes F19 or F20?
    • A
      Allison AllenSep 15, 2025
      This can happen if there is a battery charger fault. Open the battery fuse holders (SWBATT), insert the maintenance bypass (SWMB) and shut down the UPS completely. Switch on again and if the fault persists, contact the nearest technical support centre.
  • J
    Jerome LongSep 5, 2025
    Why won't my Riello MCT 10 start and shows codes A30, A32, A33, or A34?
    • M
      Morgan KerrSep 5, 2025
      If the Riello UPS displays codes A30, A32, A33, or A34 and will not start, it might be because the ambient temperature is below 0°C. Heat the environment, wait for the heat sink temperature to rise above 0°C, and then start up the UPS. Another cause may be a fault in the temperature probe on the heat sink. Activate the maintenance bypass (SWMB), turn the UPS off and on again and exclude the maintenance bypass. If the problem persists, call your local service centre.
  • J
    Jerry MckinneySep 2, 2025
    What does C01 mean on my Riello MCT 10 display?
    • H
      huffstephenSep 3, 2025
      The code C01 on the Riello UPS display indicates that the jumper is missing from the R.E.P.O. connector (J13) or is not inserted correctly. Assemble the jumper or check that it is inserted correctly.

Summary

Multi Sentry UPS Overview

UPS Electrical Connections Overview

UPS Control Panel Interface

Installation Procedures

UPS Storage and Installation Preparation

Provides recommendations for storing the UPS and preparing the installation environment.

Electrical Connections and Wiring Diagrams

Details electrical connection requirements and provides wiring diagrams for system integration.

Using the UPS

UPS Description and Block Diagram

Explains the purpose of a UPS, its functionality, and provides a block diagram of its main components.

Preliminary Operations Before Power-On

Outlines essential preliminary operations, including visual checks and closing fuse holders.

First-Time Power-On Procedure

Guides the user through the initial power-on sequence for the UPS, including phase checks.

UPS Power-On and Power-Off Procedures

Details the procedures for powering the UPS on from mains or battery, and for powering it off.

Operating Modes and Maintenance Bypass

Describes different operating modes (ECO, SMART ACTIVE) and the procedure for maintenance bypass.

UPS Software and Management

Covers the PowerShield³ monitoring software and the configuration software for UPS management.

Configuring the UPS

Configuration Options via Control Panel and Software

Details configurable parameters like frequency, voltage, operating modes, and alarms via control panel or software.

Advanced Function Settings and Parameters

Details advanced configuration options such as frequency tolerance, bypass thresholds, and power walk-in.

Troubleshooting Guide

Common UPS Problems and Solutions

Provides solutions for common UPS operational issues, including power, standby, and battery problems.

Technical Data

UPS Input and Output Stage Specifications

Provides detailed technical specifications for the UPS input and output stages across different models.

UPS Dimensions, Modes, and Battery Box Data

Details UPS dimensions, operating modes, efficiency, noise, and technical data for the battery box.

Riello MCT 10 Specifications

General IconGeneral
Apparent Power10 kVA
Active Power9 kW
Frequency50/60 Hz
Communication InterfaceRS232, USB, SNMP (optional)
Operating Temperature0°C to 40°C
Input Voltage400 V
Output Voltage230 V
TechnologyOn-line double conversion
Efficiencyup to 95%
Battery TypeValve Regulated Lead Acid (VRLA)