C
ONFIGURING THE
UPS
The following table shows all possible configurations available to tailor the UPS to your needs in the best way possible.
CP
(Control Panel) = Indicates that the configuration can be edited not only by the configuration software but also using the
control panel (if function editing is enabled on the panel).
SW
(Software) = Indicates that the configuration can be changed from the configuration software only.
FUNCTION DESCRIPTION DEFAULT POSSIBLE CONFIGURATIONS MOD.
Output frequency
Selecting the rated output
frequency (for the setting to
be active, turn the UPS off
then back on)
50 Hz
50 Hz
60 Hz
CP
Output Voltage
Selects nominal Output
voltage (Phase / Neutral)
230V
200V *
208V *
220V
230V
240V
CP
220 ÷ 240 in steps of 1V
SW
Operating Mode
Selects one of the 5
operating modes
ON LINE
ON LINE
ECO
SMART ACTIVE
STAND-BY OFF
CP
FREQUENCY CONVERTER
SW
Power off due to
minimum load
Automatically switches off
the UPS in battery operation
when the load is less than
5%
Disabled
Enabled
Disabled
CP
Autonomy
limitation
Sets the maximum time of
battery operation
Disabled
Disabled (complete battery
discharge)
1 ÷ 65000 in steps of 1 sec.
SW
Low battery
pre-alarm
Sets the estimated autonomy
time left for low battery
warning
3 min.
1 ÷ 255 in steps of 1 min.
(1 to 7 min from the panel)
SW
Battery test
Sets the interval of time for
the automatic battery test
40 hours
Disabled/Enabled (from the panel)
1 ÷ 1000 in steps of 1 hour
SW
Maximum load
alarm threshold
Selects the user overload
limit
Disabled
Disabled
0 ÷ 103 in steps of 1%
SW
Sound alarm
Selects the operating mode
of the sound alarm
Reduced
Normal
Reduced: does not sound because of
momentary intervention of the bypass
CP
Auxiliary socket
(power share)
Selects the operating mode
of the auxiliary socket
Always
connected
Always connected
Disconnected after n seconds of
battery operation
Disconnected after n seconds from the
end-of-discharge alarm signal
... (see configuration software manual)
SW
Battery expansion
Sets the Ah installed
(external battery extension)
0 Ah
Min.: 0 - Max.: 999
(in steps of 1 Ah)
CP
Language**
Selects the display language English
English
Italian
German
French
Spanish
Polish
Russian
Chinese
CP
Date and time
Sets the date and time -- --
CP