20033333 (5) - 02/2013
Installation, use and maintenance instructions
Gas oil burners
Progressive two-stage or modulating operation
CODE MODEL TYPE
20032806 - 20034204 RL 70/M 669 T1
20032813 - 20034206 RL 100/M 670 T1
20032818 - 20034272 RL 130/M 671 T1
GB

Table of Contents

Questions and Answers

  • J
    Jeffrey RaySep 10, 2025
    Why won't my Riello RL BI0 Burner go to 2nd stage?
    • R
      Raymond MathewsSep 10, 2025
      If the Riello Burner does not pass to the 2nd stage, it could be because control device TR does not close, so adjust or replace it. It could also be due to a defective control box, so replace it.
  • J
    Jared SmithSep 12, 2025
    Why does Riello Burner pump lose prime?
    • K
      Kelly CollinsSep 12, 2025
      If the pump loses prime after a prolonged pause in your Riello Burner, it could be because the return pipe is not immersed in fuel, so bring it to the same height as the suction pipe. Alternatively, air might be entering the suction piping, so tighten the connectors.
  • T
    Tyler AcevedoSep 13, 2025
    What causes a Riello RL BI0 to stop and lock out during operation?
    • D
      Dr. Ashley PalmerSep 13, 2025
      If the burner stops in lock out during operation, it may be due to a dirty or defective photocell, so clean or replace it.
  • J
    Jeffrey MitchellSep 15, 2025
    Why is my Riello RL BI0 Burner pump leaking oil?
    • D
      danielcolemanSep 15, 2025
      If the pump leaks light oil in your Riello Burner, it's likely due to leakage from the sealing organ, so replace the pump.
  • D
    destinybutlerSep 18, 2025
    What causes an internally rusted pump in Riello RL BI0 Burner?
    • R
      Rebecca PierceSep 18, 2025
      If the pump is internally rusted, it may be due to water in the tank, so remove the water from the tank bottom with a separate pump.
  • B
    Brittany PatelNov 24, 2025
    What to do if Riello RL BI0 Burner locks out after pre-purge?
    • T
      Tammy SmithNov 25, 2025
      If your Riello Burner locks out after pre-purge and the safety time, and no flame appears, consider these potential causes: There might be no fuel in the tank, or water at the tank bottom, so top up the fuel level or remove the water. The head and air damper adjustments might be inappropriate, requiring adjustment. The light oil solenoid valves could be failing to open, so check connections and replace the coil if necessary. The nozzle might be clogged, dirty, or deformed, so replace it. The firing electrodes might be dirty or poorly adjusted, so adjust or clean them. The electrode could be grounded due to broken insulation, so replace it. The high voltage cable could be defective or grounded, or deformed by high temperature, so replace it and protect it. The ignition transformer could be ...