TECHNICAL DATA
(1) Reference conditions: Ambient temperature 68 °F (20 °C) - Barometric pressure 394” WC - Altitude 329 ft.
(2) Pressure at test point 17)(A)p.4, with zero pressure in the combustion chamber, with open gas ring 2)(B)p.6 an maximum burner output
(3) Sound pressure measured in manufacturer’s combustion laboratory, with burner operating on test boiler and at maximum rated output.
Burner models designations
:
A
CCESSORIES
(optional):
•
Kit for LPG operation:
The kit allows the RS 190/M burners to operate on LPG.
•
Gas train according to UL regulation:
see page 9.
MODEL RS 190/M
Output
(1)
MAX. kW 1420 - 2542
4845 - 8673
MBtu/hr
MIN. kW 522
1781
MBtu/hr
Fuel Natural or Propane gas
- max. delivery SCFH 8673
- pressure at max. delivery
(2)
“ WC 5.9
Operation Low - high or modulating
Standard applications Boilers: water, steam, thermal oil
Ambient temperature °F 32 - 104 (0 - 40 °C)
Combustion air temperature °F max 140 (60 °C)
Main electrical supply (+/- 10%) V/Ph/Hz 208 - 230/460/575/3/60
Fan motor rpm
W - HP
V
A
3400
4000 - 5.5
208-230/460/575
15.8 - 9.1 - 7.3
Ignition transformer V1 - V2
I1 - I2
120 V - 1 x 7 kV
1.6 A - 23 mA
Electrical power consumption W max 5500
Electrical protection NEMA 1
Noise levels
(3)
dBA 83.1
Model
Code Voltage Flame Safeguard
RS 190/M
C9527300
(3787670)
C9527301
(3787670)
C9627300
(3787672)
C9627301
(3787672)
208-230/460/3/60
575/3/60
208-230/460/3/60
575/3/60
Burner mounted
Remote panel
Burner mounted
Remote panel
BURNER
RS 190/M
Output kW
MBtu/hr
516 - 2542
1761 - 8673
Code 3010276
Important:
The installer is responsible for the supply and installation of any safety device(s) not indicated in this manual.