6.6 Pressure switch adjustment
6.6.1 Maximum gas pressure switch
Adjust the maximum gas pressure switch (Fig. 29) after making
all other burner adjustments with the maximum gas pressure
switch set to the end of the scale.
To calibrate the maximum gas pressure switch, open the tap and
then connect a pressure gauge to its pressure test point.
The maximum gas pressure switch must be regulated to a value
no higher than 30% of the measurement read on the gauge when
the burner is working at maximum output.
After making the adjustment, remove the pressure gauge and
close the tap.
6.6.2 Minimum gas pressure switch
Adjust the minimum gas pressure switch (Fig. 30) after perform-
ing all the other burner adjustments with the pressure switch set
to the start of the scale.
With the burner operating at maximum output, increase adjust-
ment pressure by slowly turning the relative knob clockwise until
the burner stops.
Now turn the knob anticlockwise by 0.2 kPa (2 mbar) and repeat
burner start-up to ensure it is uniform.
If the burner locks out again, turn the knob anticlockwise again by
0.1 kPa (1 mbar).
6.6.3 PVP pressure switch kit
Adjust the pressure switch for the leak detection control (PVP
kit)(Fig. 31) according to the instructions supplied with the kit.
WARNING
1 Kpa = 10 mbar