41
20163082
GB
Start-up, calibration and operation of the burner
The value 1 appears on the display screen:
After approx 8 seconds (it depends on the duration of the pro-
gramme), the 0 value appears on the display screen, this is to in-
dicate that the restore process has been completed correctly.
NOTE:
When the restore process is successfully completed, the 0
value is shown on the display screen.
Err C information: 136 D: 1 (restore process initialised) is
displayed for a brief moment.
6.10.3 List of parameters
D12145
h
mi n
s
%
P
V
D12143
h
mi n
s
%
P
V
At the end of the restore process, it is neces-
sary to check the sequence of functions and
the list of parameters.
Parameter
No. of
elements
Unit of
measure-
ment
Modifica-
tion
Values interval
Degree of
precision
Predefined
setting
Access mode
No. Description Min. Max.
000 INTERNAL PARAMETERS
050
Start backup/restore process via RDI21... / PC TOOL
(set the parameter to 1)
Index 0 = create backup
Index 1 = perform restore
Negative values indicate errors
2 - Modification -99 2 1 0; 0 Service mode
055
Burner identification number created from the backup
on RDI21...
1 - Reading only 0 99999999 1 0 Service mode
056 ASN number created by the backup on RDI21... 8 - Reading only 0 127 1 0 Service mode
057 Software Version created by the backup on RDI21... 1 - Reading only 0x100 0xFFF9 1 0 Service mode
100 GENERAL PARAMETERS
102 Control box identification date 1 - Reading only 0 255 1 Info mode
103 Control box identification number 1 - Reading only 0 65535 1 Info mode
104 Identification number of the group of parameters set 1 - Reading only 0 255 1 30 Info mode
105 Version of the group of parameters set 1 - Reading only 0 0xFFFF 1 V01.08 Info mode
107 Software version 1 - Reading only 0 0xFFF9 1 V03.30 Info mode
108 Software variation 1 - Reading only 0 225 1 1 Info mode
111
ASN number to verify the ASN number created by the
backup on RDI 21…
8 - Reading only 0 127 1 0 Service mode
113 Burner identification 1 - Modification 0 99999999 1 Not defined
Info Mode
with password
Service Mode
121
Manual setting of output
Not defined = automatic operation
1 %
Modification /
zero setting
0% 100% 0.1% Not defined Info mode
123
Minimum output step position
Index 0: BACS output
Index 1: output of the external load regulator,
analogue.
Index 2: output of the external load regulator contacts.
3 % Modification 0% 100% 0.1% 0%; 1%; 0% Service mode
124
Beginning flame loss test (TÜV test)(define the
parameter at 1)(switch of flame loss fuel valves) A
negative value indicates an error (see code 150)
1 - Modification -6 1 1 0 Service mode
125
Frequency of main power supply
0 = 50 Hz
1 = 60 Hz
1 - Modification 0 1 1 0 Service Mode
126 Brightness of display 1 % Modification 0% 100% 1% 75% Service Mode
128
Fuel meter: Led pulse valence
(led pulses / volumetric flow units)
1 - Modification 0 400 0,01 0 Service Mode
130
Eliminate visualisation error chronology
To eliminate the visualisation, set the parameter to 1,
then to 2
Answer 0: process successful
Answer -1: timeout of 1_2 - sequence
1 - Modification -5 2 1 0 Service Mode