Start-up, calibration and operation of the burner
133
Default output for TÜV test:
Not valid for TÜV test when output is activated
2,000 ..... 10,000 = low flame or first / second / third
stage
1 %
Modification /
zero setting
20% 100% 0.1% Not defined Service Mode
141
Remote management of control box
0 = off
1 = Modbus
2 = reserved
1 - Modification 0 2 1 0 Service Mode
142
Standby time before a new attempt in event of com-
munication fault
Set values:
0 = not active
1 = .... 7200 s
1 s Modification 0s 7200s 1s 120s Service Mode
143 Reserved 1 - Modification 1 8 1 1 Info Mode
144 Reserved 1 s Modification 10s 60s 1s 30s Service Mode
145
Peripheral address for Modbus
Set values:
1 ... 247
1 - Modification 1 247 1 1 Service Mode
146
Baud Rate for Modbus
Set values:
0 = 9600
1 = 19200
1 - Modification 0 1 1 1 Service Mode
147
Parity for Modbus
0 = none
1 = odd
2 = even
1 - Modification 0 2 1 0 Service Mode
148
Selection of the burner operation during the interrup-
tion of the switch-over with the system of remote man-
agement.
Set values:
With modulating operation the settings of the values
are the following:
0...19.9 = burner switched off
20...100 = 20...100% modulation field of the burner.
With stage operation:
0 = burner off P1, P2, P3
No setting = no function in the event of communication
interruption
1 %
Modification /
zero setting
0% 100% 0.1% Not defined Service Mode
161 Total number of errors 1 - Reading only 0 65535 1 0 Info mode
162 Hours of operation (that can be reset) 1 h Reset 0 h 999999h 1 h 0h Info mode
163 Total hours of power supply to control box 1 h Reading only 0h 999999h 1h 0h Info mode
164 Total number of start-ups (that can be reset) 1 - Reset 0 999999 1 0 Info mode
166 Total number of start-ups 1 - Reading only 0 999999 1 0 Info mode
167
Volumetric delivery of fuel in the selected unit of meas-
urement (that can be reset)
1
m
3
, l,
ft
3
, gal
Reset 0 99999999 1 0 Info mode
200 BURNER CHECKS
201
Burner operation mode (fuel supply line, modulating/
stage, servomotors, etc.)
-- = not defined (eliminate curves)
1 = Gmod
2 = Gp1 mod
3 = Gp2 mod
4 = Lo mod
5 = Lo 2 stage
6 = Lo 3 stage
7 = Gmod pneu
8 = Gp1 mod pneu
9 = Gp2 mod pneu
10 = LoGp mod
11 = LoGp 2-stage
12 = Lo mod 2 fuel valves
13 = LoGp mod 2 fuel valves
14 = G mod pneu without actuator
15 = Gp1 mod pneu without actuator
16 = Gp2 mod pneu without actuator
17 = Lo 2-stage without actuator
18 = Lo 3-stage without actuator
19 = G mod only gas actuator
20 = Gp1 mod only gas actuator
21 = Gp2 mod only gas actuator
22 = Lo mod only oil actuator
1 -
Modify/set to
zero
1 22 1 Not defined Service Mode
Parameter
No. of
elements
Unit of
measure-
ment
Modifica-
tion
Values interval
Degree of
precision
Predefined
setting
Access mode
No. Description Min. Max.