51
20163082
Faults - Possible causes - Solutions
2 Valve leak detection test not possible
The valve leak detection is active, but the minimum gas
pressure switch is selected as input for X9-04 (check
parameters 238 and 241).
3 Valve leak detection test not possible
The valve leak detection is active, but no input has been
assigned (check parameters 236 and 237).
4 Valve leak detection not possible
Valve leak detection is active, but 2 inputs have already been
assigned (configure parameter 237 or maximum gas Pressure
switch or POC).
5 Valve leak detection not possible
The valve leak detection is active, but 2 inputs have been
assigned (check parameters 236 and 237).
14 # POC
0 POC Open Check if the closure contact of the valve is closed.
1 POC Closed
Check the wiring.
Check if the closure contact of the valve opens when the valve
is checked.
64 POC Open - Alarm lockout at start
Check the wiring.
Check if the closure contact of the valve is closed.
19 80 Fuel pressure, POC - Alarm lockout at start
Check that the pressure switch is closed when no pressure is
present from the fuel.
Check that there are no short-circuits.
20 # Pmin
0 Minimum gas/oil pressure absent Check that there are no line interruptions.
1 Scarcity of gas - Alarm lockout at start Check that there are no line interruptions.
21 # Pmax/POC
0
Pmax: Max. gas/oil pressure exceeded
POC: POC open (software version V02.00)
Check the wiring.
POC: check whether the closure contact of the valve is closed.
1 POC closed (software version V02.00)
Check the wiring.
Check if the closure contact of the valve opens when the valve
is checked.
64
POC Open - Lockout alarm at the start (software version
V02.00)
Check the wiring.
Check if the contact of the valve opens when the valve is
checked.
22
OFF S
# Safety circuit/Burner flange
0 Safety circuit open /Burner flange open
1
Safety circuit open /Burner flange open - Alarm lockout at
start
3
Safety circuit open /Burner flange open, extraneous light -
Alarm lockout at start
5
Safety circuit open /Burner flange open, extraneous light -
Alarm lockout at start
17
Safety circuit open /Burner flange open, extraneous light -
Alarm lockout at start
19
Safety circuit open /Burner flange open, extraneous light -
Alarm lockout at start
21
Safety circuit open /Burner flange open, extraneous light -
Alarm lockout at start
23
Safety circuit open /Burner flange open, extraneous light,
air pressure, fuel pressure - Alarm lockout at start
65
Safety circuit /Burner flange open, POC - Alarm lockout at
start
67
Safety circuit open /Burner flange open, extraneous light,
POC - Alarm lockout at start
69
Safety circuit open /Burner flange open, air pressure, POC
- Alarm lockout at start
71
Safety circuit open /Burner flange open, extraneous light,
air pressure, POC - Alarm lockout at start
81
Safety circuit open /Burner flange open, fuel pressure, POC
- Alarm lockout at start
83
Safety circuit open /Burner flange open, extraneous light,
air pressure, POC - Alarm lockout at start
85
Safety circuit open /Burner flange, air pressure, fuel
pressure, POC - Alarm lockout at start
87
Safety circuit open /Burner flange, extraneous light, air
pressure, fuel pressure, POC - Alarm lockout at start
Error
code
Diagnostic code Meaning of the REC 37.400A2 system Recommended measures