24
TECHNICAL DATA
Maximum operating voltage
Recharge time (standard versions)
Expandability and nominal
voltage of the Battery Box
Charging current
(for ER versions only)
Selectable: 220 / 230 / 240
Selectable: 50, 60 or auto sensing
Overload: 100% < load < 110%
Bypass line available: activates the bypass after 2 seconds
locks after 120 seconds
Bypass line not available: locks after 60 seconds
Overload: 110% < load < 150%
Bypass line available: activates the bypass after 2 seconds
locks after 4 seconds
Bypass line not available: locks after 4 seconds
Bypass line available: activates the bypass instantly
locks after 1 second
Bypass line not available: locks after 0.5 seconds
< 90% without condensation
excessively low batteries - overcurrent - short circuit - overvoltage -
undervoltage - circuit breaker
Weight (for ER versions only)
For more details please consult the web site
(1)
at nominal load, nominal voltage of 230 Vac, battery charging
(2)
If the mains frequency is within ±5% of the selected value, the UPS is synchronised with the mains. If the frequency is
out of the tolerance range or operating from the battery, the frequency is the one selected ±0.1%
(3)
20 - 25 °C for longer battery life
(4)
To keep the output voltage within the indicated range of precision, recalibration may be necessary after a long period
of operation