EasyManua.ls Logo

Rish DELTA VAF NX - Page 29

Rish DELTA VAF NX
43 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
29
Device Address
Function Code
Start Address High
Start Address Low
Number of Registers Hi
Number of Registers Lo
CRC Low
CRC High
01 (Hex)
10 (Hex)
17 (Hex)
72(Hex)
00 (Hex)
02(Hex)
61 (Hex)
CA (Hex)
Start address high : Most significant 8 bits of starting address of
the parameter requested.
Start address low : Least significant 8 bits of starting address of
the parameter requested.
Number of register hi : Most significant 8 bits of number of
registers requested.
Number of register lo : Least significant 8 bits of number of
registers requested.
(Note : Two consecutive 16 bit register represent one
parameter.)
Response:
Table 4 : 4 X register addresses
46003 System Type 3 1: 1P2W, 2: 3P3W, 3: 3P4W, 4: 1P3W
46005 PT Primary 415 100 to 1200KVLL
46007 CT Primary 5 1 to 9999
46009 PT Secondary 415 100 to 500 VLL
46011 CT Secondary 5 1 or 5
46015 - -
46031 Reset Parameters 0 0 to 7
46033 Password 0 0000 to 9999
46035 Factory Reset 0 5555
46039 No Of Poles 2 2 to 40 (multiples of 2 only)
46041 Autoscroll 0 0 or 1
46043 Noise Cutoff 0 0mA or 30mA
46045 Comsetup 8 4 to 23
46047 Modbus Address 1 1 to 247
46049 Register Order 0 2141
46055 Relay 1 Out Select 0 0 for NONE, 2 for Limit
46059 Limit 1 Conf Sel 0 0: Hi-En, 1: Hi-DEn, 2: Lo-En. 3: Lo-DEn
46061 Limit 1 Trip Point 100 See Table 4
46063 Limit 1 Hysteresis 50 0.5% to 50%
46065 Limit 1 On Delay 1 1 to 10
46067 Limit 1
Address Description Defaul t Val ues Setting Range
Off Delay 1 1 to 10
46085 Version No.

Related product manuals