This address is used to set the System Type.
Write one of the following value to this address.
1 =1 Phase 2 Wire 4=1 Phase 3 Wire
2 = 3 Phase 3 Wire
3 = 3 Phase 4 Wire
Writing any other value will return error.
This address allows the user to set PT Primary value.
The maximum settable value is 1200kVL-L for all System Types &
also depends on the per phase 1000MVA restriction of power
combined with CT primary.
This address allows the user to set CT Primary value.
The maximum settable value is 9999 & also depends on the per
phase 1000MVA Restriction of power combined with PT primary
This address is used to read and write the PT secondary value.
Ref Table for the range of PT secondary settable values in
Section 3.2.1.3
This address is used to read and write the CT secondary value.
write one of the following values to this address.
1=1A CT secondary
5=5A CT secondary
writing any other value will return an error.
The following screens allow the users to reset the all
1.Lo(Min), 2.hi(Max) ,4.Run hour, 5.On hour, 6.Number of
Interrupts, 7.Reset ALL
This address is used to set & reset the password.
Valid Range of Password can be set is 0000 - 9999 .
1) If password lock is present & if this location is read it will return
zero.
2) If Password lock is absent & if this location is read it will return
One.
3) If password lock is present & to disable this lock first send
valid
Address Parameters Description
46003 System Type
46005 PT Primary
46007 CT Primary
46009 PT Secondary
46011 CT Secondary
46015 -
46031 Reset Parameters
46033 Password
46035 Factory Reset
password to this location then write ā0000ā to this location
4) If password lock is present & to modify 4X parameter first
send valid password to this location so that 4X parameter will be
accessible for modification.
5) If for in any of the above case invalid password is send then
meter will return exceptional error 2.
sending 5555 to this address will Reset meter to factory defalts.