31
Enables to set No. of poles of a Generator of which RPM is to be
measured and to which the instrument is connected to monitor its
parameters.
setting range is 2 to 40 (multiples of 2 only)
This address is used to activate or de-activatethe auto scrolling.
Write 0-Deactivate 1-Activate, Writing any other value will return
an error.
This address is used to set the noise current cutoff. The valid
values are 0 OR 30 (mA).
This address is used to set the baud rate, Parity, Number of stop
bits. Refer to Table 6 for details.
Word Order controls the order in which Multifunction Meter
receives or sends floating - point numbers:- normal or reversed
register order . In normal mode, the two registers that make up a
floating point numbers are sent most significant bytes first. In
reversed register mode , the two registers that make up a floating
point numbers are sent least significant bytes first. To set the
mode, write the value ā€˜2141.0’ into this register-the instrument will
detect the order used to send this value and set that order for all
ModBus transaction involving floating point numbers.
This address is used to select the Relay operation as pulse or
Limit.
write one of the following values to this address.
=None = Limit output on Relay.
Writing any other value will return an error
This address is used to assign the Parameter to Relay
If Limit option is selected refer table 2 for parameter number.
This address is used to set the Configuration
46039 No Of Poles
46041 Autoscroll
46043 Noise Cutoff
46045 Comsetup
46047 Modbus Address
46049 Word Order
46055 Relay 1 Out Select
46057 Limit 1 Para Sel
46059 Limit 1 Configuration Sel
46061 Limit 1 Trip Point
46063 Limit 1 Hysteresis
46065 Limit 1 On Delay
for relay see table 8.
Writting any other value will return an error.
This address is used to set the trip point in %. Tje values for high
and low alarm can be refered from Table 2.
Writing any other value will return an error.
This address is used to set the hysteresis between 0 to 50 .
Writing any other value will return an error.
This address is used to set the Energizing delay between 1 to 10 .
Writing any other value will return an error.
This register address is used to set Device address between 1 to
247 .
0 ,2