40 RITTAL outdoor cooling unit assembly and operating instructions
9 Technical specifications
9 Technical specifications
Tab. 5: Technical specifications
Unit
Model No. CS
Outdoor cooling unit –
9761.212 9762.212 9768.152
Rated voltage
V
Hz
230, 1~,
50/60
Rated current A 3.58 4.0 5.8
Start-up current A 10.8 10.6 19.0
Pre-fuse T A 10.0
Dimensions (W x H x D) mm 515 x 1170 x 152 535 x 390 x 400 400 x 1050 x 310
Position – Wall mounting Roof mounting
Door- and wall-mounted unit,
partial internal mounting
Minimum dimensions CS modular enclosure
(W x H or D x H)
mm 600 x 1200 600 x 500 600 x 1200
Material (enclosure) – Sheet steel Aluminium
Surface finish (enclosure) –
Powder-coated in RAL 7035
Pure polyester
Useful cooling output
Q
k
L 35 L 35
to DIN 3168 L 35 L 50
W
W
900 (50 Hz)
750 (50 Hz)
900 (50 Hz)
750 (50 Hz)
1500 (50 Hz)
1250 (50 Hz)
Power consumption P
el
L 35 L 35
to DIN 3168 L 35 L 50
W
W
450 (50 Hz)
520 (50 Hz)
460 (50 Hz)
520 (50 Hz)
940 (50 Hz)
1045 (50 Hz)
Heater W 400 400 800
Refrigeration factor ε = Q
k
/P
el
– 2.0 1.95 1.6
Refrigerant
– Type
– Filling
–
g
R134a
600
R134a
550
R134a
650
Admissible pressure bar 24 27 28
Power per fan, unimpeded air flow
– external circuit
– internal circuit
m
3
/h
m
3
/h
800
800
570
570
680
880
Temperature setting range °C –33 to +55
Weight kg 45 29 40
Protection category to EN 60 529
(external circuit – internal circuit)
–IP 55
Type of connection – Via connector panel
.
.