Technical Specifications
UPS-Manual
29
EN
Model 1KVA 2KVA 3KVA
Battery System
Type 12V/7,2Ah 12V/7,2Ah 12V/9Ah
Numbers of Batteries 3 6 6
Backup Time(100%) >7min. >7min. >5min.
Backup Time(80%) >9min. >10min. >9min.
Backup Time(60%) >14min. >14min. >12min.
Backup Time(40%) >27min. >22min. >19min.
Backup Time(20%) >55min. >66min. >45min.
Recharging Time 4 Hours to 90%
Charging Current (Max.) 1,8A 2,1A 2,7A
Charging Voltage 41,0Vdc±0,5V 82,0Vdc±0,5V 82,0Vdc±0,5V
Hot Swappable Battery
Yes
Internal battery
Yes
DC leakage current
30µA (±10µA) with no AC applied and the unit in the off position
Battery type
Sealed, non-spillage, maintenance-free, lead acid
Transfer Time
AC to DC Zero
Inverter to Bypass 2,5ms(Typical) Zero
DC Start Yes
Self Diagnostics By button of the panel or Software Control
Front Panel
LED
Load Level/Battery Level/ Battery Mode/ Normal Mode/Bypass Mode/ Self-Test/
Weak/Bad Battery/Site Wiring Fault/ Fault/ Overload/Programmable
Outlet1//Programmable Outlet2
Key
ON Button/ OFF Button/ (Test/Alarm Reset Button)
Protection
(AC Mode )
<105% continuous
>106% ~ 120% for 30 seconds transfer to bypass
>121% ~ 150% for 10 seconds transfer to bypass
>150% for immediately transfer to bypass
Buzzer continuously alarms.
Overload
(Battery Mode)
<105% continuous
>106% ~ 120% for 30 seconds shuts down
>121% ~ 150% for 10 seconds shuts down
>150% for immediately shuts down
Buzzer continuously alarms.

Table of Contents

Other manuals for Rittal PMC12

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rittal PMC12 and is the answer not in the manual?

Rittal PMC12 Specifications

General IconGeneral
BrandRittal
ModelPMC12
CategoryUPS
LanguageEnglish

Related product manuals