Heating engineer
Installation, use and maintenance manual – M gas unit heater
19
3
II
2Esi3P
FR
20 25 37
II
2Er3P
20 25 37
II
2H3B/P
HU
25 30 30
II
2HS3B/P
25 25 30 30
II
2E3P
LU 20 50
II
2L3B/P
NL
25 30 30
II
2L3P
25 37
II
2EK3B/P
20 25 30 30
II
2EK3P
20 25 30
II
2E3B/P
PL
20 37 37
I
2E
20
II
2ELwLs3B/P
20 13 20 37 37
II
2ELwLs3P
20 13 20 37
I
2E(R)
BE
20 25
I
2E(S)
20 25
I
3P
37
I
3P
IS 30
I
2H
LV 20
I
3B/P
MT
30 30
I
3B
30
The appliance gas supply pressure, both static and dynamic, must comply with the values in the Table, with a tolerance of ± 15%.
3.2.5 Vertical pipes and condensate
Vertical gas pipes must be tted with siphon and dis-
charge of the condensate that may form inside the
pipe.
If necessary, insulate the piping.
3.2.6 LPG pressure reducers
With LPG the following must be installed:
A rst stage pressure reducer, close to the liquid gas
tank.
A second stage pressure reducer, close to the appli-
ance.
3.3 COMBUSTION PRODUCTS EXHAUST
Compliance with standards
The appliance is approved for connection to a
combustion products exhaust duct for the types
shown in Table 1.2
p.14
.
3.3.1 Flue gas exhaust connection
Ø 110 mm, on the rear side, at the top (see dimension-
al drawings in the 1.2
p.8
Section).
3.3.2 Combustion air intake tting
Ø 130 mm, on the rear side, at the top (see dimension-
al drawings in the 1.2
p.8
Section).
3.3.3 Installation types
If ducts other than those supplied by the manufac-
turer are used, make sure that they are suitable for
the unit on which they are installed. In particular,
the temperature class of the duct must be ap-
propriate for the operating characteristics of the
unit, and must also respect the chemical-physical
stability of the system itself.
In any case, use approved ducts according to the
type of installation to be made. Upon request,
Robur can supply rigid pipes, coaxial ducts and ter-
minals, all of approved type.
Gas unit heaters of the M series can be installed to one of
the following ways.
3.3.3.1 B22 type installation with wall ue gas exhaust
pipe
Figure3.1 B22 type installation with wall ue gas exhaust pipe