Surge transient immunity IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth CM) on DC power
ports
±2 kV line-earth (CM) on shielded Ethernet port
Conducted RF immunity IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM
from 150 kHz…80 MHz
Magnetic field immunity IEC 61000-4-8:
30 A/m long duration and 300 A/m short duration
at 50 and 60 Hz
Certifications
Certifications (when
product is marked)
(1)
Value
CE European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers
(Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:
-AS/NZS CISPR11; Industrial Emissions
EtherNet/IP ODVA conformance tested to EtherNet/IP specifications
c-UL-us UL Listed Industrial Control Equipment, certified for US and
Canada. See UL File E356258.
UL Listed for Class I, Divison 2 Group A,B,C,D Hazardous
Locations, certified for US and Canada.
See UL Files E356259.
(1)
See the Product Certification link at http://www.ab.com for Declarations of Conformity,
Certificates, and other certification details.
Environmental Specifications
Attribute 9300-ENA