EasyManua.ls Logo

Rockwell Automation Allen-Bradley Guardmaster 442G-MABE1

Rockwell Automation Allen-Bradley Guardmaster 442G-MABE1
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
44 Rockwell Automation Publication 442G-UM002B-EN-P - August 2021
Appendix B EtherNet/IP I/O Assemblies
Tag Definitions
Name
Signal
Rating
Data
Type
Tag Definition
ConnectionFaulted
Standard
BOOL
Connection Faulted — Indicates the state of the communication connection between the access box and the controller.
0 = Connection to the tag is up and working
1 = Not connected
CycleThresholdExceeded BOOL
Cycle Threshold Exceeded— indicates when the module has reached 1,000,000 switching cycles
0 = < 1,000,000 switching cycles of the solenoid
1 = > 1,000,000 switching cycles of the solenoid
Note: Prognostic information only. This tag is not a fault condition.
DiagnosticActive BOOL
Diagnostic Active — Indicates whether the access box is faulted.
1 = One or more diagnostics active
0 = No diagnostics active
EnablingSwitch Safety BOOL
Enabling Switch (GripSwitch) Status
1 = Enabling is in the active (enabled) state
0 = Switch is released (safe state)
EnablingSwitchFault Standard BOOL
Enabling Switch (GripSwitch) Fault — indicates an Enabling Switch specific fault
1 = Fault
0 = OK, no fault
Note: This tag rolls up into DiagnosticActive.
EStop Safety BOOL
E-stop Status
1 = E-stop is in the active state (E-stop not pressed)
0 = E-stop pressed (safe state)
EStopFault Standard BOOL
E-stop Fault — indicates an E-stop-specific fault
1 = Fault
0 = OK, no fault
Note: This tag rolls up into Diagnostic Active.
EStopLight BOOL
E-stop Light — controls illumination for the E-stop.
1 = Illumination is turned ON
0 = Illumination is turned OFF
FaultCode INT Fault Code — indicates the specific diagnostic message of the access box
GeneralFaultUnlatch BOOL
General Fault Acknowledgment — unlatches faults that are related to the bus interface
1 = Reset of bus module
0 = Normal operation
GuardClosed Safety BOOL
Guard Position Monitoring — indicates the position of the guard
1 = Guard is closed
0 = Guard is open
GuardInterlocked BOOL
Interlock Status
1 = Guard is interlocked (guard closed with bolt actuator engaged)
0 = Bolt is retracted (disengaged) and/or guard is open
GuardLocked BOOL
Guard Locking Status
1 = Guard locking is active (guard is closed, actuator (bolt) is engaged AND locked)
0 = Guard locking is not active (actuator (bolt) is NOT engaged and NOT locked)
Light<X> BOOL
Light X — controls illumination of the push button in location <x>
1 = Illumination is turned ON
0 = Illumination is turned OFF
X= 4, 6, 7, 9 switch element designator
LockSequenceFaultUnlatch Standard BOOL
Lock Sequence Fault Acknowledgment — unlatches faults that are related to the locking sequence
1 = Reset of locking assembly
0 = Normal operation
LockSequenceFault BOOL
Lock Sequence Fault — indicates a signal sequence error
1 = Fault
0 = OK, no fault
Note: This tag rolls up into Diagnostic Active.
RunMode BOOL
Run Mode — Indicates the operating mode of the access box
1 = Run Mode
0 =Not Run Mode
Switch<X> Standard BOOL
Switch X for momentary push button:
1 = Push Button Pressed
0 = Push Button Released
X=4, 6, 7, 9 switch element designator
Unlock Safety BOOL
Unlock Command — control for switching the guard locking on and off.
1 = Turn guard locking OFF (disable locking)
0 = Turn guard locking ON (enable locking)
Note: Logic is the same for both Power to Lock (PTL) and Power to Release (PTR) versions
UnlockCommandFault Standard BOOL
Unlock Command Fault — indicates a fault in the Unlock Command
1 = Fault
0 = OK, no fault
Note: This tag rolls up into Diagnostic Active.

Table of Contents

Other manuals for Rockwell Automation Allen-Bradley Guardmaster 442G-MABE1

Related product manuals