Step 2: Validate the Drive Installation
Verify the Setting of the ENABLE and SAFETY Jumpers
• If the ENABLE jumper is removed, then to enable the product to operate, you must apply control power to the
main control board, port 0 TB1 terminal <Di0> and <DiC>. No modification of drive parameters is required.
Port 0 TB1 terminal <Di0> becomes the dedicated product enable input. For more information, see the
PowerFlex 750-Series Products with TotalFORCE Control Installation Instructions, publication 750-IN100
.
• If the SAFETY jumper is removed, install the ENABLE jumper and install a safety option module in a valid
control pod port. Configuring a safety option module is beyond the scope of this document. See the manual for
the safety option that is installed:
– Catalog number 20-750-S: PowerFlex 750-Series Safe Torque Off User Manual, publication 750-UM002
.
– Catalog number 20-750-S1: Safe Speed Monitor Option Module for PowerFlex 750-Series AC Drives Safety
Reference Manual, publication 750-RM001
.
– Catalog number 20-750-ATEX: PowerFlex 750-Series ATEX Option Module User Manual,
publication 750-UM003
.
– Catalog number 20-750-S3: PowerFlex 755 Integrated Safety - Safe Torque Off User Manual,
publication 750-UM004
.
– Catalog number 20-750-S4: PowerFlex 755/755T Integrated Safety Functions Option Module, publication
750-UM005
.
Figure 2 - Main Control Board
Item Name Description
1 HIM Connector DPI port 01 (HIM Cradle) connection.
2 Fan Connector Power supply for internal cooling fan.
3 Control Selector Rotary switch for setting the programming mode.
4 Embedded EtherNet/IP
(1)
Address Selectors
(1) See the PowerFlex Drives with TotalFORCE Control Built-in EtherNet/IP Adapter User Manual,
publication 750COM-UM009
.
Rotary switches for setting lowest octet of EtherNet address
(forces address to 192.168.1.xxx). See Configure Embedded
EtherNet/IP Communication Adapter on page 26 for instructions
on setting the IP address.
5 SAFETY Jumper Safety enable jumper. Removed when safety option is installed.
6 ENABLE Jumper Hardware enable jumper. TB1 becomes an Enable when this
jumper is removed.
7 Built-in EtherNet/IP
Adapter
A single adapter with dual EtherNet/IP network cable
connections.
8TB1 I/O terminal block.
9 DPI port 2/3 Cable connection for handheld and remote HIM options.