Rockwell Automation Publication 750-QS100B-EN-P - August 2020 19
Step 3: Power Up, Configure the Modular Control Profiles
Power the Drive
Use one of the following procedures to energize your drive.
For Drives Without 24V Auxiliary Power
1. Energize the 3-phase power source to the drive.
2. For Frames 7…15, turn the Fused Disconnect handle on the drive input bay to the ON position.
3. After the drive boots up, if there are any faults, correct and clear them.
For Drives With 24V Auxiliary Power
1. Energize the three-phase power source to the drive.
2. For Frames 7…15, turn the Fused Disconnect handle on the drive input bay to the ON position.
3. After the drive boots up, if there are any faults, correct and clear them.
4. Energize the 24V Auxiliary Power supply source.
5. Keep the 24V Auxiliary Power source energized even if the AC power is de-energized. This maintains operation of
the control pod port devices and communication adapters.
ATTENTION: Power must be applied to the drive to perform the following start-up procedure. Some of the voltages present are
at incoming line potential. To avoid electric shock hazard or damage to equipment, allow only qualified service personnel to
perform the following procedure. Thoroughly read and understand the procedure before beginning.
TIP The drive should remain energized for the next procedure, but if you ever want to de-energize the drive, do so as follows:
1. For Frames 7…15, turn the Fused Disconnect handle on the drive input bay to the OFF position.
2. De-energize the 3-phase power source to the drive.
TIP The drive should remain energized for the next procedure, but if you ever want to de-energize the drive, do so as follows:
1. For Frames 7…15, turn the Fused Disconnect handle on the drive input bay to the OFF position.
2. De-energize the 3-phase power source to the drive.