Rockwell Automation Publication 750-RM100A-EN-P - August 2019 109
Application References Chapter 11
Configure the Motor Side Inverter
1. Stay at port 10, which is the port for Motor Side Inverter Control.
2. Navigate to parameter 10/11:110 [Mtr Stop Mode A] and enter a value
of 'Ramp' (1).
3. Navigate to parameter 10/11:229 [Regen Power Lim] and enter a value
of -200%.
4. Navigate to parameter 10/11:204 [Mtr OL Hertz] and enter a value that
reflects the cooling capacity of the motor. See parameter 10/11:204 [Mtr
OL Hertz].
5. Navigate to parameter 10/11:220 [Drive OL Mode] and enter a value of
‘Reduce PWM’ (2).
6. Navigate to parameter 10/11:222 [Current Limit 1] and enter a value
equal to 200% of motor nameplate amps.
7. Navigate to parameter 10/11:256 [OutPhaseLossActn] and enter a value
of ‘FltCoastStop’ (3).
8. Navigate to parameter 10/11:116 [Bus Reg Mode A] and enter a value of
0‘Disabled’.
9. Navigate to parameter 10/11:913 [Autotune Trq Lim] and enter a value
of 100%.
Configure the Motor Encoder Feedback
1. Stay at port 10, which is the port for Motor Side Inverter Control.
2. Navigate to parameter 10/11:1000 [Pri Vel Fb Sel]. Select the encoder
feedback on the feedback card in port 5.
If you are following the guidelines at the beginning of this procedure (with
a 20-750-ENC-1 in slot 5), the resulting value is 50004 ‘Port 5: Enc 0 FB’.
Then enter the two-digit port number for feedback option card, and the
four-digit parameter number for the parameter that displays the feedback.
3. Navigate to parameter 10/11:1013 [PReg Fb Sel]. Then enter the same
value that you used for 10/11:1000 [Pri Vel Fb Sel].
4. Navigate to the port that contains the feedback option card. That would
be port 5 when using a 20-750-ENC-1 in slot 5.
5. Configure the parameters on the feedback option card to match the
encoder you are using.
Parameters 5:1 [Encoder Cfg] and 5:2 [Encoder PPR] when using a 20-
750-ENC-1 in slot 5.
6. Confirm the value of parameter 5:3 [Fdbk LossCfg] is 3 ‘FltCoastStop’.