Rockwell Automation Publication 750-RM100A-EN-P - August 2019 49
Predictive Maintenance Chapter 6
Control Pod Fan Example
Follow these steps to reset the Elapsed Life and Remaining Life parameters for
the pods on the control pod.
1. Go to port 0 and open parameter 0:504 [PredMain Rst En]. Set bit 0 ‘Port
0’.
2. Stay in port 0, and go to parameter 0:505 [Pred Maint Reset]. Then select
1 ‘PodFan Life’.
Parameter 0:505 [Pred Maint Reset] returns to 0 ‘Ready’ after the reset is
performed.
3. Return to parameter 0:504 [PredMain Rst En] in port 0. Then clear bit 0
‘Port 0’.