52 Rockwell Automation Publication 750-RM100A-EN-P - August 2019
Chapter 6 Predictive Maintenance
Control Pod Fan Example
Go to the Predictive Maintenance group in the Protection file of port 0.
Go to parameter 0:514 [PodFan EventLevel]. Change the value to 70%.
Now the control pod fan event occurs when 70% of the fan life is consumed.
Go to parameter 0:515 [PodFan EventActn]. The value is set to ‘Alarm’ with an
internal value of 1.
When set to alarm, a Control Pod Fan event results in a numbered alarm with
text.