Rockwell Automation Publication PFLEX-AP005A-EN-P - October 2010 39
Drive Selection Considerations Chapter 1
PowerFlex 700 Drives I/O Cassette Terminals
Table 15 - PowerFlex 700 Drives I/O Control Terminal Designations (Frames 0…6)
Terminal Name Factory Default Description
1 Analog In 1 (–)
(1) (4)
Isolated
(5)
, bipolar, differential, ±10V/0-20 mA, 11 bit & sign
For 0-20 mA, a jumper must be installed at terminals 17 & 18 (or 19 & 20)
88 k ohm input impedance when configured for volt & 95.3 ohm for current
2 Analog In 1 (+)
(1)
3 Analog In 2 (–)
(1)
4 Analog In 2 (+)
(1)
5 Pot Common – For (+) and (–) 10V pot references
6 Analog Out 1 (–)
(4)
Single-ended bipolar (current output is not bipolar), ±10V/0-20mA, 11 bit &
sign, Voltage mode - limit current to 5 mA. Current mode - max. load is 400
ohms
7 Analog Out 1 (+)
8 Analog Out 2 (–)
9 Analog Out 2 (+)
10 HW PTC Input 1 – 1.8k ohm PTC, Internal 3.32k ohm pull-up resistor
11 Digital Out 1 – N.C.
(2)
Fault Max. Resistive Load:
240V AC/30V DC – 1200VA, 150W
Max. Current: 5A, Min. Load: 10 mA
Max. Inductive Load:
240V AC/30V DC – 840VA, 105W
Max. Current: 3.5A, Min. Load: 10 mA
12 Digital Out 1 Common
13 Digital Out 1 – N.O.
(2)
NOT Fault
14 Digital Out 2 – N.C.
(2)
NOT Run
15 Digital Out 2/3 Com.
16 Digital Out 3 – N.O.
(2)
Run
17 Current In Jumper
(1)
–
Analog In 1
Placing a jumper across terminals 17 & 18 (or 19 & 20) will configure that
analog input for current
18
19 Current In Jumper
(1)
–
Analog In 2
20
21 –10V Pot Reference – 2k ohm minimum load
22 +10V Pot Reference –
23 HW PTC Input 2 – See above
24 +24V DC
(6)
– Drive supplied logic input power
(6)
25 Digital In Common –
26 24V Common
(6)
– Common for internal power supply
27 Digital In 1
(3)
Stop - CF 115V AC, 50/60 Hz - Opto isolated
Low State: less than 30V AC
High State: greater than 100V AC, 5.7 mA
24V DC
- Opto isolated
Low State: less than 5V DC
High State: greater than 20V DC, 10 mA DC Digital Input Impedance: 21k ohm
28 Digital In 2
(3)
Start
29 Digital In 3
(3)
Auto/Man.
30 Digital In 4
(3)
Speed Sel 1
31 Digital In 5
(3)
Speed Sel 2
32 Digital In 6/Hardware
Enable
(3)
Speed Sel 3
(1) Important: 0-20 mA operation requires a jumper at terminals 17 & 18 (or 19 & 20). Drive damage may occur if jumper is not installed.
(2) Contacts in unpowered state. Any relay programmed as Fault or Alarm will energize (pick up) when power is applied to drive and deenergize (drop out) when a fault or
alarm exists. Relays selected for other functions will energize only when that condition exists and will deenergize when condition is removed.
(3) A 10 k Ohm, 2 W burden resistor must be installed on each digital input when using a triac-type device. The resistor is installed between each digital input and neutral/
common.
(4) These inputs/outputs are dependant on a number of parameters. For more information, see Chapter 3, Programming and Parameters, in the PowerFlex 700 AC Drives User
Manual, publication 20B-UM002
.
(5) Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides high common mode immunity.
(6) 150 mA maximum Load. Not present on 115V versions.
16
32
1
17