62 Rockwell Automation Publication PFLEX-AP005A-EN-P - October 2010
Chapter 2 Analog Speed Follower and Preset Speed
Preset Speeds
The following tables depict the binary pattern for the drive speed-select digital
inputs.
Table 32 - PowerFlex Drives Digital Input (DI) Preset Speeds
PowerFlex 700 Drive Preset Speeds PowerFlex 755 Drive Preset Speeds
123
Auto Reference Source DI Speed Sel 2 DI Speed Sel 1 DI Speed Sel 0 Auto Reference Source
0 0 0 Reference A 0 0 0 Reference A
0 0 1 Reference B 0 0 1 Reference A
0 1 0 Preset Speed 2 0 1 0 Reference B
0 1 1 Preset Speed 3 0 1 1 Preset Speed 3
1 0 0 Preset Speed 4 1 0 0 Preset Speed 4
1 0 1 Preset Speed 5 1 0 1 Preset Speed 5
1 1 0 Preset Speed 6 1 1 0 Preset Speed 6
1 1 1 Preset Speed 7 1 1 1 Preset Speed 7
IMPORTANT
Speed-select input functionality changed with the PowerFlex 755 drive,
which impacts how a PowerFlex 700 drive is migrated.