26
Publication 1763-IN001C-EN-P - June 2015
Off-State Leakage
Current
2.5 mA max. 1.5 mA max.
Nominal
Impedance
12 kΩ at 50 Hz
10 kΩ at 60 Hz
3.1 kΩ 3.1 kΩ
Inrush Current
(max.) at 120V ac
250 mA Not Applicable
(1)
OS Series B FRN 4 or later
Digital Input Specifications for 1763-L16DWD
Description 1763-L16DWD
Inputs 0 through 3
(4 high-speed dc inputs)
Inputs 4 and higher
(6 standard dc inputs)
On-State Voltage Range 10...24V dc at 65 °C/149 °F)
(10...30V dc at 30 °C/86 °F)
Off-State Voltage Range 0...5V dc
Operating Frequency
0 Hz...40 kHz
(1)
(1)
OS Series B FRN 4 or later.
0 Hz...1 kHz
On-State Current:
minimum
nominal
maximum
2.0 mA at 10V dc
8.5 mA at 24V dc
12.0 mA at 30V dc
Off-State Leakage Current 1.5 mA max.
Nominal Impedance 2.61 kΩ 3.1 kΩ
Maximum Inrush Current Not Applicable
Digital Inputs
Description 1763-L16AWA 1763-L16BWA, -L16BBB
Inputs 0 through 3
(4 high-speed dc inputs)
Inputs 4 and higher
(6 standard dc inputs)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation MicroLogix 1100 Series and is the answer not in the manual?

Rockwell Automation MicroLogix 1100 Series Specifications

General IconGeneral
BrandRockwell Automation
ModelMicroLogix 1100 Series
CategoryController
LanguageEnglish

Related product manuals