EasyManua.ls Logo

Rockwell DeviceNet - Page 90

Default Icon
102 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
C-22
VSM500 DeviceNet Option Board
State Transition Diagram
The following State Transition Diagram provides a graphical description of the states
and state transitions that are reflected in attribute #6.
Run/Stop Event Matrix
Attribute 5, NetCtrl, is used to request that Run/Stop events be controlled from the
network. Before Run/Stop control is accomplished from the network, Attribute 15,
CtrlFromNet must be set to 1 by the device in response to a NetCtrl request.
If attribute 15, CtrlFromNet is set to 1, the events Run and Stop are triggered by a
combination of the RunFwd and RunRev attributes as shown in the following table.
Important: When attempting to use attribute 3 or 4 to start the drive, the Explicit
Message connection (Class 5, instance 1) attribute 9, Expected Packet
Rate must be set to greater than zero.
Figure C.1 – State Transition Diagram
RunFwd RunRev Trigger Event Run Type
00StopNA
0 -> 1 0 Run RunFwd
0 0 -> 1 Run RunRev
0 -> 1 0 -> 1 No Action NA
1 1 No Action NA
1->0 1 Run RunRev
1 1->0 Run RunFwd
Switch Power On
Ready
Enabled
Faulted
Switch Power Off
Fault Reset
Fault Detected
Fault Detected
Stop Complete
Run
Non-Existent
Stopping
Fault Detected
No Run
Run

Table of Contents