Part No 4801-5156 Rev 1-2017 RollSeal SC-325 & SC-650 Controllers Page 13
Actual Position
Open Speed
Close Speed
TotalCycles
Service Cycles
Door Obstruction
(Cycles 100)
Mode
Up/Down Arrows
Mode
Safety Beam Obstructed
5 Smart Controller User Interface
5.1 The Power Switch
The Power Switch of the Smart Controller is located on the left side of the controller box as illustrated on the
previous page. The switch controls power to the Smart Controllers and to the automatic doors. The Main
Fuse is located on the outside, bottom-left of the enclosure.
Warning!
DO NOT Turn The Power ON Until All Of The Following Items Are Completed:
All Wire And Cable Connections Are Completed.
The Voltage Selection Switch And Jumper Are Set To Match The Required Supply
Voltage.
The Motor Brake Rectifier Is Wired Accordingly To Match The Required Supply
Voltage.
Refer to Section 6.3 for Switch Settings information. Refer to Section 11.1 (for V1) or 11.3 (for V2) and 11.5
for the location of SWX2 on PCB 154 and J1 on the Motor Drive board assembly. Refer to Section 12.2 for
specific RS-500/600 Motor Brake Rectifier wiring diagrams.
5.2 The Display Indicator
The Display Indicator can show four
different types of readings that can be
selected by pressing the Mode button on
the Display. Each time the Mode button
is depressed the display steps to the next
parameter as indicated by the green LED
next to the display.
The four readings on the Display
Indicator selected by using the Mode
button are:
Actual Position – The position of the door curtain in relative position units called Counts. See Section 4.1 for
a description of Counts. A low Count reading indicates that the door is at the top or open
position. The highest Count reading is when the door is at the bottom or closed position.
Open Speed – The percentage of full speed that the door will open. The full speed will depend on the type
of drive motor installed. This can be changed from a low of 20 percent to a high of 100
percent.
Close Speed – The percentage of full speed that the door will close. The full speed will depend on the
type of drive motor installed. This can be changed from a low of 20 percent to a high of 75
percent.
Total Cycles – The total number of times (cycles) that the door has been opened and closed. The value
displayed is in units of 100 cycles. For example a reading of 20 means that the door has
been operated between 2000 and 2099 times.
Service Cycles – The number of times (cycles) that the door has been opened and closed since the last service
reset. The value displayed is in units of 100 cycles. For example, a reading of 20
represents between 2000-2999 cycles. This cycle count is used for service purposes. Refer
to Section 6.1 for information on how to reset this count and how to set Service
Reminders.
To view each of the four parameters, press the Mode button repeatedly until the green LED on the Display
Indicator shows the desired parameter to be read or changed. Use the Up/Down arrows to adjust the Speed
percentage to the desired setting. To read the number of times the door has been cycled, press the Mode
button until the green LED beside Cycles (x100) is lighted. To return to the Actual Position, press the Mode
button again, or wait a few seconds and the controller will automatically return to displaying Actual Position.
There is an LED on the Display Indicator that will light when the Safety beam is interrupted. See Section
5.3.7 for more discussion on the function of the Safety Beam.
!