22
Reference Manual
00809-0100-4378, Rev CE
Appendix B: Product Certifications
February 2014
Product Certifications
B.2.2 Europe
E8 ATEX Flameproof
Certificate: DEKRA11ATEX0240X
Standards Used: EN 60079-0:2009, EN 60079-1:2007
Markings: II 2 G Ex d IIC T5/T6 Gb, T6(-20 °C T
a
+40 °C), T5(-20 °C T
a
+70 °C)
Special Condition for Safe Use (X):
The original manufacturer shall be contacted for information on the dimensions of the
flameproof joints.
I8 ATEX Intrinsic Safety
Certificate: Baseefa03ATEX0448X
Standards Used: EN 60079-0:2009, EN 60079-11:2007
Markings: II 1 G Ex ia IIC T5/T6 Ga; T6(-60 °C T
a
+40 °C), T5(-60 °C T
a
 +80 °C)
Special Condition for Safe Use (X):
The apparatus enclosure may contain light metals. The apparatus must be installed in such
a manner as to minimize the risk of impact or friction with other metal surfaces.
N1 ATEX Type n
Certificate: Baseefa03ATEX0454
Standards Used: EN 60079-0:2009; EN 60079-15:2010
Markings: II 3 G Ex nA IIC T6 Gc; (-40 °C T
a
+70 °C)
B.2.3 International
E7 IECEx Flameproof
Certificate: IECEx DEK 11.0082X
Standards Used: IEC 60079-0:2007-10; IEC 60079-1:2007-04
Markings: Ex d IIC T5/T6 Gb, T6(-20 °C T
a
 +40 °C), T5(-20 °C T
a
+70 °C)
Special Condition for Safe Use (X):
The original manufacturer shall be contacted for information on the dimensions of the
flameproof joints.
I7 IECEx Intrinsic Safety
Certificate: IECEx BAS 11.0064X
Standards Used: IEC 60079-0: 2011; IEC 60079-11: 2011
Markings: Ex ia IIC T5/T6 Ga; T6(-60 °C T
a
 +40 °C), T5(-60 °C T
a
 +80 °C)
Special Condition for Safe Use (X):
The enclosure may be made of aluminum alloy and given a protective polyurethane or
epoxy polyester paint finish; however, care should be taken to protect it from impact or
abrasion if located in a Zone 0 environment.