4
Reference Manual
00809-0100-4378, Rev CE
Section 1: Introduction
February 2014
Introduction
1.2 Analog meter
The analog meter requires an analog 4–20 mA dc, 10–50 mA dc, or 40–200 mV dc transmitter
output from a two-wire transmitter. Several meter calibration options are available to suit the
requirements of a particular application. Linear 0 to 100 percent meter scaling is adequate for
the majority of applications. A logarithmic 0 to 100 percent scale is available for use with flow
transmitters. As an option, the user can specify special meter scaling for direct readout in psi,
gph, °F, °C, or other convenient engineering units.
The large 2
1
/4-inch diameter meter face has a two-inch long scale for easy readability as shown in
Figure 1-2. A meter-zero adjustment is located on the meter faceplate. The meter can be
rotated in 90° increments within the enclosure for convenient viewing.
Figure 1-2. Analog Meter
Analog Meter Face
PERCENT
0
20
40
60
80
100