EasyManua.ls Logo

Rosslare AC-215IP - Input and Output Connections; Input Types; Normally Open Input Connection

Rosslare AC-215IP
37 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Input and Output Connections
20 AC-215IP Hardware Installation Manual
4. Input and Output Connections
This chapter describes the AC-215IP access control panel's input and output
connections.
4.1 Input Types
There are four input types Normally Open, Normally Closed, Normally Open
Supervised 1 or 2 resistors, and Normally Closed Supervised 1 or 2 resistors.
Inputs IN1, IN1A, IN2 and IN2A may be configured individually as either
supervised or non-supervised inputs. Configure each input separately via the
AxTraxNG™ system.
Non-supervised inputs have two states:
Normal State
Abnormal State
Supervised inputs have three states:
Normal State
Abnormal State
Trouble State
The Trouble state is caused by either tampering with the input circuit or by
faulty hardware installation. Once configured as supervised input, add a
resistor of 2.2K, of 8.2K, or both on the input circuit. See the figures in the
following subsections.
4.1.1 Normally Open Input Connection:
Normally Open Input has 2 states:
Switch Open Normal State:
Loop resistance = Infinite (open circuit)
Switch Closed Abnormal State:
Loop resistance = 0 (short circuit)

Table of Contents

Related product manuals