Page #21 background imageLoading...
Page #21 background image
Input and Output Connections
AC-215IP Hardware Installation Manual 21
Figure 9: Normally Open Input Connection
4.1.2 Normally Closed Input Connection
Normally Closed Input has two states:
Switch ClosedNormal State:
Loop resistance = 0 (short circuit)
Switch Open Abnormal State:
Loop resistance = Infinite (open circuit)
Figure 10: Normally Closed Input Connection
4.1.3 Normally Open Supervised Single Resistor Input Connection
Connect a resistor of 8.2K in parallel to the input switch contacts.
Normally Open Supervised Input has 3 states:
Switch OpenNormal State:
Loop resistance = 8.2K
Switch Closed Abnormal State:
Loop resistance = 0 (short circuit).
Open circuit across input terminalsTrouble State:
Loop resistance = Infinite (open circuit).