EasyManua.ls Logo

Rosslare AC-215IP - Technical Specifications; Electrical Characteristics; Communication Characteristics; Environmental Characteristics

Rosslare AC-215IP
37 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Specifications
AC-215IP Hardware Installation Manual 11
2. Technical Specifications
Electrical Characteristics
Operating Voltage
12 VDC 1.5 A from PS-14
Maximum Input Current
Standby: 120 mA
Maximum: 370 mA
General Inputs
4 supervised high impedance inputs.
Maximum voltage: 5 VDC
Relay Outputs
4 relay outputs
5 A Relay N.O. and N.C. options
Reader Ports
2 reader ports
Output voltage: 12 VDC
Max. current: 300 mA
LED control output D0/D1, tamper input
Visual Indicators
11 LEDs
Audio
Built in sounder (bell, chime and siren)
Battery Standby Time
3 hours (with 12 V, 7 Ah battery)
Communication Characteristics
RS-232
Terminal block
RS-485
Molex and terminal block
TCP/IP
On-board RJ-45 connector
Speed Options
9600 bps
19200 bps
57600 bps
115200 bps
Environmental Characteristics
Operating Temperature Range
32°F to 120°F (C to 49°C)
Operating Humidity
0 to 85% (non-condensing)
Dimensions
Height x Width x Depth
10.4 x 13.2 x 3.4 in. (264 x 334 x 84.5 mm)
Weight
8.38 lbs. (3.81 kg)
Transformer (for AC-215IP only)
AC Transformer
120/220 VAC, 16 VAC 2.5 A (40 VA)

Table of Contents