EasyManua.ls Logo

Rosslare AC-215IP - Normally Closed Supervised Single Resistor Input Connection; Normally Closed Supervised Double Resistor Input Connection

Rosslare AC-215IP
37 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Input and Output Connections
AC-215IP Hardware Installation Manual 23
4.1.5 Normally Closed Supervised Single Resistor Input Connection
Connect a resistor of 2.2K in series to the input switch contacts.
Normally Closed Supervised Input has 3 states:
Switch ClosedNormal State:
Loop resistance = 2.2K
Switch Open Abnormal State:
Loop resistance = Infinite (open circuit)
Short circuit across input terminalsTrouble State:
Loop resistance = 0 (short circuit)
Figure 13: Normally Closed Supervised Input (Single Resistor)
4.1.6 Normally Closed Supervised Double Resistor Input Connection
Connect a resistor of 2.2K in series to the input switch contacts.
Connect a resistor of 8.2K parallel to the input switch contacts.
Normally Closed Supervised Input has 3 states:
Switch ClosedNormal State:
Loop resistance = 2.2K
Switch Open Abnormal State:
Loop resistance = 10.4K
Open circuit (Infinite loop resistance) or short circuit (0 resistance) across
input terminalsTrouble State

Table of Contents

Related product manuals