8 x Faults and malfunctions
104
FA ROTEX HeatPumpSolarUnit - Part 2 - 05/2009
Hot water does not warm up
Water heating switched off (e.g. time program is in the
economy phase, parameters for water heating have
been set incorrectly).
Check the operating mode setting.
Check the request parameters.
Hot water does not heat up
enough.
Storage tank charging temperature too low. Increase the target hot water temperature.
Draw-off rate too high. Reduce the draw-off rate, limit throughput.
Output of heat pump too low.
Check the switching times for room heating and water heating
for overlaps.
Backup Heater (BH) not switched on as well.
Check mains supply of the Backup Heater (BH).
Thermal protection switch for the Backup Heater (BH) has been
triggered (see Chapter2.2.1 "Indoor Module (RKHB)", item 20).
Overheating fuse for the Backup Heater (BH) is defective (see
Chapter2.2.1 "Indoor Module (RKHB)", item 21).
Check parameter values [4-XX].
Optionally installed ROTEX Solaris system Change parameter settings [C-00].
Booster Heater (EHS)
Check mains supply of the Booster Heater (EHS).
Check position of the STL on the Booster Heater (EHS) (see
Fig 4-72, Page 53).
Check parameter settings [8-XX]:
Room cooling
1)
is not cooling
Water flow too low.
Check that all stop valves of the water circuit are completely
open.
Check that the water filter is dirty.
Check that the expansion tank is defective.
Bleed system completely.
Check on pressure gauge whether there is sufficient water
pressure >0.3 bar.
Check that the pump speed is set to the highest level.
Check that the resistance in the water circuit is not too high for
the pump (see Chapter5.1.5 "Starting up a ROTEX HeatPump-
SolarUnit").
Room cooling
1)
standby switched off (e.g. switching
time program is in economy phase, outside tempera-
ture too high)
Check the operating mode setting.
Check the request parameters.
Check the setting of time a weekday in the control system.
Refrigerant compressor is not working.
Wait until minimum water temperature is reached (15 °C). At a
low water temperature the system uses the Backup Heater (BH)
first to reach the minimum water temperature.
Have the system checked by a service engineer.
System is in the operating mode "Room heating" Reset operating mode to "Room cooling".
Cooling output for room
cooling
1)
too low
Water flow too low.
Check that all stop valves of the water circuit are completely
open.
Check whether the water filter is dirty.
Check whether the expansion tank is defective.
Bleed system completely.
Check on pressure gauge whether there is sufficient water
pressure >0.3 bar.
Check if the pump speed is set to the highest level.
Check that the resistance in the water circuit is not too high for
the pump (see Chapter5.1.5 "Starting up a ROTEX HeatPump-
SolarUnit").
Quantity of refrigerant in the system too low or too
high.
Have quantity of refrigerant checked by a service engineer and
have the system checked for leaks at the same time.