www.rotexautomation.com
➢ Cable gland
o ¼” NPT
o M20 x 1.5
➢ Weight (with gauges)
o Bare Positioner option 1,5 = 2.25 kgs /5 lbs
o Bare Positioner option 2,6 = 2.5 kgs / 5.5 lbs
o Bare Positioner option 3 = 6.6 kgs / 10.6 lbs
o Bare Positioner option 4,7 = 9.9 kgs / 21.9 lbs
o Positioner transmitter /Alarm module = 0.08 kgs / 0.2 lbs
• Pneumatics
➢ Supply pressure
o 1.4 to 8 bar / 0 to 14 psi (10 bar on request)
➢ Capacity with 4 bar / 60 psi
o > 1 to 41 Nm³/h / 0.5 to 23 scfm (servo controlled orifice)
➢ Consumption with 4 bar / 60 psi (Steady state)
o < 1 lpm / 0.037 scfm @ 4 bar
• Instrument Air
➢ Air Quality
o In accordance to ISO 8573-1
➢ Solid particles
o Class 5 (maximum density 3mg/m³, 5μm filtration is recommended)
➢ Humidity
o Class 1 (Dew point 10° C below minimum operating temperature)
➢ Oil
o Class 3 (maximum concentration 5 mg/m³ or < 1 ppm)