EasyManuals Logo

Rotex Posidapt Series User Manual

Rotex Posidapt Series
131 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
RTX-IOM-PRODUCT-YY
Page 10 of 131
www.rotexautomation.com
Cable gland
o ¼” NPT
o M20 x 1.5
Weight (with gauges)
o Bare Positioner option 1,5 = 2.25 kgs /5 lbs
o Bare Positioner option 2,6 = 2.5 kgs / 5.5 lbs
o Bare Positioner option 3 = 6.6 kgs / 10.6 lbs
o Bare Positioner option 4,7 = 9.9 kgs / 21.9 lbs
o Positioner transmitter /Alarm module = 0.08 kgs / 0.2 lbs
Pneumatics
Supply pressure
o 1.4 to 8 bar / 0 to 14 psi (10 bar on request)
Capacity with 4 bar / 60 psi
o > 1 to 41 Nm³/h / 0.5 to 23 scfm (servo controlled orifice)
Consumption with 4 bar / 60 psi (Steady state)
o < 1 lpm / 0.037 scfm @ 4 bar
Instrument Air
Air Quality
o In accordance to ISO 8573-1
Solid particles
o Class 5 (maximum density 3mg/m³, 5μm filtration is recommended)
Humidity
o Class 1 (Dew point 10° C below minimum operating temperature)
Oil
o Class 3 (maximum concentration 5 mg/m³ or < 1 ppm)