Threshold Limit 3
Use this sub-parameter to set the limit threshold 3.
• Off
This parameter value does not trigger any message or alarm.
• Custom
The threshold 3 fault message is displayed when the limit threshold 3 is exceeded. The value
can be set up to 100000000.
Monitoring of Average Value
Applicable for Posidapt –Super and Ultra
This parameter is used to calculate and monitor the position average.
During the test, the position and reference average values are always compared at the end
of a time interval. The device triggers a fault message if the current value exceeds one of the
three configurable limit thresholds.
The current value is displayed in the “Position Average” diagnostics parameter.
Monitoring Time
This parameter is used to set the time interval to calculate the position average.
• Value
The value can be set from 1 to 30
• Unit of value
The unit can be set as minute, day, month or year.
A position average over the time interval set in unit of value is determined and compared with
the reference average at the expiry of the time interval. The test is then restarted.
Reference value
Select this parameter to set reference value with which position average over the time interval
is compared. The value can be set from 0.0 to 100.0%.
Threshold Limit 1
This parameter is used to set threshold 1 for the maximum deviation of the current position
average from the reference average.