RTX-IOM-PRODUCT-YY
Page 106 of 131
www.rotexautomation.com
Off
This parameter value does not trigger any message or alarm.
Custom
This parameter is used to set the threshold 1 in percent. The device triggers a fault message
if the difference between the position average and the reference average exceeds threshold
1. The value can be set from 0.1 to 100.0%.
Threshold Limit 2
This parameter is used to set threshold 2 for the maximum deviation of the current position
average from the reference average.
Off
This parameter value does not trigger any message or alarm.
Custom
This parameter is used to set the threshold 2 in percent. The device triggers a fault message
if the difference between the position average and the reference average exceeds threshold
2. The value can be set from 0.1 to 100.0%.
Threshold Limit 3
This parameter is used to set threshold 3 for the maximum deviation of the current position
average from the reference average.
Off
This parameter value does not trigger any message or alarm.
Custom
This parameter is used to set the threshold 3 in percent. The device triggers a fault
message if the difference between the position average and the reference average exceeds
threshold 3. The value can be set from 0.1 to 100.0%.
Counter Trends
Average Set point Change
This parameter is used to calculate and monitor the set point change average.
Off
This parameter value does not trigger any message or alarm.
Custom