www.rotexautomation.com
• Off
This parameter value does not trigger any message or alarm.
• Custom
This parameter is used to set the threshold 1 in percent. The device triggers a fault message
if the difference between the position average and the reference average exceeds threshold
1. The value can be set from 0.1 to 100.0%.
Threshold Limit 2
This parameter is used to set threshold 2 for the maximum deviation of the current position
average from the reference average.
• Off
This parameter value does not trigger any message or alarm.
• Custom
This parameter is used to set the threshold 2 in percent. The device triggers a fault message
if the difference between the position average and the reference average exceeds threshold
2. The value can be set from 0.1 to 100.0%.
Threshold Limit 3
This parameter is used to set threshold 3 for the maximum deviation of the current position
average from the reference average.
• Off
This parameter value does not trigger any message or alarm.
• Custom
This parameter is used to set the threshold 3 in percent. The device triggers a fault
message if the difference between the position average and the reference average exceeds
threshold 3. The value can be set from 0.1 to 100.0%.
Counter Trends
Average Set point Change
This parameter is used to calculate and monitor the set point change average.
• Off
This parameter value does not trigger any message or alarm.
• Custom