Mode on Start-up
Applicable for Posidapt Modern, Expert, Super, Ultra and IPST
Mode on start-up function enables to choose in which operating the device should start in
after restart or input signal failure.
Auto - Factory default
This parameter will start the device in auto mode.
Manual
This parameter will start the device in manual mode.
Last Mode
This parameter will resume the device in last mode it was being operated.
Fail Safe Action
Defines what action takes place when there is a loss of signal pressure.