www.rotexautomation.com
This parameter is used to cut off unusable range of the control valve from the point of control.
• Off – Factory Default
In this mode the valve will follow the input signal linearly. The valve start position is same as
the actual start position of the actuator determined during auto calibration.
• Custom
This parameter is used to cut off start position (0.0%) unusable range of the control valve. It
is the percentage of the working range to which to which the valve is moved with minimum
input signal to move valve forward.
The value can be set from 0.0 to 20.0%
Dead Angle Maximum
Applicable for Posidapt – Modern, Expert, Super, Ultra and IPST