Higher Temperature Monitoring
Applicable for Posidapt Super and Ultra
This parameter is used to continuously monitor the maximum temperature recorded inside
the enclosure. The current temperature in the enclosure is recorded by a sensor on the main
circuit board.
The maximum temperature recorded is displayed in the “Maximum temperature recorded”
diagnostics parameter. The device triggers a fault message if the current value exceeds one
of the three configurable limit thresholds.
Threshold Limit 1
This parameter is used to set the temperature threshold 1. The device triggers a fault
message if the current temperature inside the enclosure exceeds threshold 1.
Off
This parameter value does not trigger any message or alarm.
Custom
This sub-parameter value is used to monitor the upper limit temperature. Set the threshold in
a range from "- 60.0 °C" to "130.0 °C" or "- 76.0 °F" to "266.0 °F".
Threshold Limit 2
This parameter is used to set the temperature threshold 2. The device triggers a fault
message if the current temperature inside the enclosure exceeds threshold 2.
Off
This parameter value does not trigger any message or alarm.
Custom
This sub-parameter value is used to monitor the upper limit temperature. Set the threshold in
a range from "- 60.0 °C" to "130.0 °C" or "- 76.0 °F" to "266.0 °F".
Threshold Limit 3
This parameter is used to set the temperature threshold 3. The device triggers a fault
message if the current temperature inside the enclosure exceeds threshold 3.
Off
This parameter value does not trigger any message or alarm.
Custom