Operation manual
19
RKHBH/X016BB
Indoor unit and options for air to water heat pump system
4PW62577-1 – 10.2010
6 Installation related setting
00 Installation related setting
01 Installation related setting
02 Not applicable. Do not change the default value.
Scheduled storage and reheat domestic water heating
03 Scheduled time storage 1 (ON) 0/1 1
04 Scheduled time storage start time 1:00 0:00~23:00 1:00 hour
05 Scheduled time reheat or continuous reheat 0 (OFF) 0/1/2 1
06 Scheduled time reheat start time 15:00 0:00~23:00 1:00 hour
07 Domestic hot water reheat set point 45 30~50 1 °C
08 Domestic hot water reheat set point hysteresis 10 2~20 1 °C
7 Installation related setting
00 Installation related setting
01 Installation related setting
02 Installation related setting
03 Installation related setting
04 Installation related setting
8 Installation related setting
00 Installation related setting
01 Installation related setting
02 Installation related setting
03 Installation related setting
04 Installation related setting
9 Heating and cooling set point ranges
00 Heating set point upper limit 55 37~55 1 °C
01 Heating set point lower limit 25 15~37 1 °C
02 Cooling set point upper limit 22 18~22 1 °C
03 Cooling set point lower limit 5 5~18 1 °C
04 Installation related setting
Automatic set back function
05 Set back operation 0 (OFF) 0/1 1
06 Set back operation start time 23:00 0:00~23:00 1:00 hour
07 Set back operation stop time 5:00 0:00~23:00 1:00 hour
08 Leaving water set back value 2 0~10 1 °C
A Quiet mode
00 Quiet mode type 0 0/2
01 Status 3—
02 Not applicable. Do not change the default value. 1
(a)
Read only
03 Not applicable. Do not change the default value. 0
(a)
Read only
04 Not applicable. Do not change the default value. 0
(a)
Read only
b Not applicable
00 Not applicable. Do not change the default value. 0
(a)
Read only
01 Not applicable. Do not change the default value. 0
(a)
Read only
02 Not applicable. Do not change the default value. 0
(a)
Read only
03 Not applicable. Do not change the default value. 0
(a)
Read only
04 Not applicable. Do not change the default value. 0
(a)
Read only
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range Step UnitDate Value Date Value

Table of Contents

Other manuals for Rotex RKHBH016BB3V3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rotex RKHBH016BB3V3 and is the answer not in the manual?

Rotex RKHBH016BB3V3 Specifications

General IconGeneral
BrandRotex
ModelRKHBH016BB3V3
CategoryHeat Pump
LanguageEnglish

Related product manuals