RKHBH/X016BB
Indoor unit and options for air to water heat pump system
4PW62577-1 – 10.2010
Operation manual
18
Field settings table
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range Step UnitDate Value Date Value
0 User permission level
00 User permission level 3 2/3 1 —
1 Weather dependent set point
00 Low ambient temperature (Lo_A) –10 –20~5 1 °C
01 High ambient temperature (Hi_A) 15 10~20 1 °C
02 Set point at low ambient temperature (Lo_Ti) 40 25~55 1 °C
03 Set point at high ambient temperature (Hi_Ti) 25 25~55 1 °C
05 Weather dependent for cooling function
enable/disable
0 (OFF) 0/1 — —
06 Low ambient temperature (Lo2_A) 20 10~25 1 °C
07 High ambient temperature (Hi2_A) 35 25~43 1 °C
08 Set point at low ambient temperature (Lo2_Ti) 22 5~22 1 °C
09 Set point at high ambient temperature (Hi2_Ti) 18 5~22 1 °C
2 Disinfection function
00 Operation interval Fri Mon~Sun, All — —
01 Status 1 (ON) 0/1 — —
02 Start time 23:00 0:00~23:00 1:00 hour
03 Set point (only in combination with domestic hot
water tank without electrical booster heater
(RKHTS))
60 fixed 5 °C
03 Set point (only in combination with domestic hot
water tank with built-in electrical booster heater
(RKHW*))
70 55~80 5 °C
04 Interval (only in combination with domestic hot
water tank without electrical booster heater
(RKHTS))
60 40~60 5 min
04 Interval (only in combination with domestic hot
water tank with built-in electrical booster heater
(RKHW*))
10 5~60 5 min
3 Auto restart
00 Status 0 (ON) 0/1 — —
4 Space heating off temperature
00 Installation related setting
01 Installation related setting
02 Space heating off temperature 35 14~35 1 °C
03 Installation related setting
04 Not applicable. Do not change the default value. — — — —
05 Not applicable. Do not change the default value. — — — —
06 Installation related setting
07 Installation related setting
5 Installation related setting
00 Installation related setting
01 Installation related setting
02 Installation related setting
03 Installation related setting
04 Installation related setting