8000m Series
- 65 -
2 Fault record clearing
O: No operation
1: The VFD restores all the parameters (except parameters from group F2) to factory
settings.
2: The VFD clears all the recent default records.
F0.21
Parameter lock and unlock Factory Setting 0
Setting
Options
0 Unlock parameter
1 Lock parameter
0:Unlock parameter
1: Lock parameter. After being locked, all the parameters can not be changed except
F0.21.
F0.22~F0.24 Reserved
F0.25
Cooling fan running method Factory Setting 1
Setting
Options
0 Keep running when power on
1 Reserved
0: Keep running when power on. When the VFD is powered on, the cooling fan
keeps running.
1: Automatic running. When the VFD is in operation, the cooling fan is also in
operation; when the VFD stops, the cooling fan will stop after 30s’ time delay.