PDS23 Solar Pump Controller
User Manual
Version code
PDS23-EN-602000561-1702

Questions and Answers

  • K
    Katie MooreSep 23, 2025
    What to do if Keyboard without display after power on SAJ PDS23-4T004?
    • S
      Scott HutchinsonSep 23, 2025
      To solve the keyboard without display after power on problem: * Use a multimeter to measure the input voltage of the controller; check the voltage is normal. * Check if the machine has a burning smell; if there is a burning smell, please contact the agent to replace the controller.
  • J
    Jonathan HendersonAug 23, 2025
    Why does my SAJ PDS23-4T004 show an E001 IGBT module fault?
    • A
      Alicia HolmesAug 23, 2025
      An IGBT module fault (E001) in your SAJ Controller can occur due to several reasons. It may be caused by: * Too short acceleration time: Increase acceleration time. * Damaged IGBT module: Ask for support. * Malfunction caused by interference: Inspect external equipment and eliminate interference. * Improperly grounding: Check grounding wire.
  • M
    mario26Aug 25, 2025
    What to do if SAJ PDS23-4T004 Controller displays E002 over-current during acceleration?
    • B
      Brian ParrishAug 25, 2025
      If your SAJ Controller shows an E002 error (Over-current during acceleration), it could be due to: * Too fast acceleration: Increase acceleration time. * Too low input voltage: Check the input power supply or wiring. * Lower-rating controller: Replace with higher-rating controller.
  • H
    Hannah HopkinsAug 27, 2025
    Why does my SAJ PDS23-4T004 show E004 over-current at constant running speed?
    • E
      Erica MendezAug 27, 2025
      If your SAJ Controller displays error E004, indicating over-current at constant running speed, there are several potential causes: * Sudden change of load: Check the load. * Too low input voltage: Check the input power supply or wiring. * Lower-rating controller: Replace with higher-rating controller.
  • C
    Chelsea WilliamsAug 27, 2025
    What causes E003 over-current during deceleration in my SAJ Controller?
    • E
      Eric CameronAug 28, 2025
      The E003 error on your SAJ Controller, indicating over-current during deceleration, may be caused by: * Too-fast deceleration: Increase deceleration time. * Too-heavy and large-inertia load: Add proper braking units. * Lower-rating controller: Replace with higher-rating controller.
  • J
    jacksonbrandonSep 18, 2025
    What to do if DC switch trip when power on SAJ Controller?
    • M
      Marcus WilliamsSep 18, 2025
      To solve the DC switch trip when power on problem: * A multimeter can be used to check the internal circuit of the controller, if there is a short circuit, the machine has been damaged. * Check if the machine has a burning smell; if there is a burning smell, please contact the agent to replace the controller.
  • L
    lfranklinSep 15, 2025
    What does E020 well level fault mean on my SAJ Controller?
    • C
      christina10Sep 15, 2025
      If your SAJ Controller displays the E020 error, indicating a Well Level Fault, it's likely caused by: * Dry well or slow water recovery: Wait for water to recover or reinstall the pump.
  • S
    Sue ClarkSep 16, 2025
    What does E021 tank level fault before auto start mean on my SAJ PDS23-4T004 Controller?
    • J
      Juan FowlerSep 16, 2025
      If your SAJ Controller displays error E021, indicating a Tank Level Fault before auto start, it means: * High level limit is reached: Wait until water level comes below the low level limit, and then the PDS23 Solar controller will start the pump again.
  • A
    Adrian LopezSep 6, 2025
    What causes the E007 over-voltage at constant running speed error on my SAJ PDS23-4T004 Controller?
    • B
      Barbara FieldsSep 6, 2025
      If you're seeing an E007 error on your SAJ Controller, which indicates over-voltage at constant running speed, it's likely caused by: * Abnormal input voltage: Install proper input AC reactor.
  • A
    angela76Sep 3, 2025
    What to do if SAJ PDS23-4T004 displays E010 controller overload?
    • D
      Devin MooneySep 4, 2025
      If your SAJ Controller is showing an E010 error (Controller overload), it may be due to: * Too fast acceleration: Increase acceleration time. * Avoid prompt restart when trip-off.

Summary

Notes for Safe Operation

Before Installation

Safety precautions before controller installation.

Installation

Safety precautions during controller installation.

Operation

Safety precautions during controller operation.

Maintenance and check

Safety precautions for maintenance and inspection.

Others

Additional safety instructions and warranty information.

General Information

2.3 Protection Features

Electronic monitoring capabilities and automatic shutdown conditions.

Mechanical and Electrical Installation

3.2.9 System Wiring Diagram

A comprehensive diagram illustrating system connections.

Start-up and Operation

Diagnostics and Troubleshooting

5.1 Fault Codes

Catalog of error codes, their causes, and recommended remedies.

5.2 Common Faults and Remedies

Troubleshooting common operational issues and malfunctions.

5.2.1 Pump can not run

Reasons why the pump may not operate and their solutions.

5.2.2 Controller over current, overload fault

Troubleshooting controller over current and overload conditions.

5.2.3 DC switch trip when power on

Diagnosing issues related to the DC switch tripping.

5.2.4 The keyboard without display after power on

Troubleshooting problems with the controller's keyboard display.

Regular maintenance

6.1 Controller and Pump

Periodic checks and cleaning for the controller and pump.