4.5 User Definable Parameters
The parameters can be modified at stop or running status.
The parameters cannot be modified at running status.
The parameters which are actual-detecting record value and cannot be modified.
Function
Code
Function
Descriptions
Unit
Factory Setting
Modifica
tion Type
F0 Group: Basic Parameters
F0.10
Max. output
frequency
10.00600.00
Hz
50.00
F0.12
High limit of
running frequency
30.00 60.00
Hz
50.00
F0.14
Low limit of
running frequency
0.00 F0.12
Hz
20.00
F0.18
Acceleration time
0.1 3600
s
10.0
F0.19
Deceleration time
0.1 3600
s
10.0
F0.20
Default setting
0:Not restore to default
setting
1: Restore to factory setting
2:Fault record clearing
0
F2 Group: Motor Parameters
F2.01
Motor rated power
0.4 400.0
kW
Different
according to
inverter model
F2.02
Motor rated
frequency
10.00 F0.10
Hz
50.00
F2.03
Motor rated speed
0 36000
rpm
1500(Different
according to
inverter model)