5.2 Common Faults and Remedies
The PDS23 solar pump controller may have following faults or malfunctions during
operation, please refer to the following remedies.
5.2.1 Pump can not run
The main problem of the new system is that the wiring is not standardized and the
controller terminal line fallsso that the pump can not run. Sometimes the RUN
indicator light on the keyboard is bright, and the controller also has voltage output,
but may be the solar array does not have enough power to start the pump; then the
controller will attempt to start the pump every 120s. There are the following reasons
for the pump can not run:
If there is no enough sun light, and the controller's input power is not enough.
Motor wiring errors cause the pump to reverse, change the wiring.
The motor shaft vibrates and can not rotate, it may be caused by the wiring errors;
Need to re check the motor wiring.
Pumps and pipes are clogged with mud and debris, and the pump can't run
5.2.2 Controller over current, overload faultE002/3/4/10/11
The controller appears over current and overload failure may be due to the following
reasons:
The pump or pipe plug causes the pump current increase and the controller
protection; Need to pull out the pump and check
Because of the increase in operating current of the pump, which is caused by the
pump wire is too long, the controller will be protected, and the controller will be
enlarged to use.