8000m Series
- 70 -
1: Restart is allowed. This means that after powered off and powered on again, the
VFD will restore to the previous running status automatically. That is, if the VFD is
in running status before power-off, it will delay the waiting time(F1.20) of restart
after power-on next time and then start operation automatically (when controlled by
terminals, the running terminals must be in closed status),if the VFD is stopped
before power-off, it will not start automatically after powered on again.
F1.20
Waiting time of restart after
power-off
Factory Setting 0.0s
Setting Range
0.03600s
Note: when F1.19 is 1, this setting is effective.
F1.21
Over modulation option Factory Setting 0.0s
Setting Range
0.03600s
0:Over modulation function invalid
1:Over modulation function valid
This function is suitable for the working conditions that the VFD increases the
output voltage by increasing the utilization rate of its own bus bar voltage in long
term low voltage of power grid and long term overload.
5.3 F2 Group: Motor Parameters
F2.00
Drive model Factory Setting 0
Setting Options
0 General model (G)
1 Pump model (P)
Note: Users can set the parameters of this group to change model type and take
advantage of the combination of G/P. The 220V inverter only has General model
(G).
0: Suitable for the constant torque load with the appointed parameters