- 69 -
F1.10
Dead-zone time between FWD and REV Factory Setting 0.0s
Setting Range
0.03600s
The transient time at zero output frequency in the process of setting the FWD and
REV transient process
As below:
Schematic Diagram of the Dead Time between FWD and REV
F1.11
Terminals control option when power on Factory Setting 0
Setting Options
0 Disabled
1 Enabled
F1.12-F1.17 Reserved
F1.18
Wake-up delay time (effective in sleep and
standby mode)
Factory Setting 0.0s
Setting Range
0.03600s
When F0.15=2, only if the time that the set frequency is equal or greater than the
lower limit frequency exceeds the set vale of F1.18 can the VFD begin to operate.
F1.19
Restart option after power-off Factory Setting 0
Setting Options
01
0: Restart is prohibited. This means that after powered off and powered on again, the
VFD will not start automatically.