EasyManuals Logo

SAJ 8000m Series User Manual

SAJ 8000m Series
153 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #72 background imageLoading...
Page #72 background image
8000m Series
- 71 -
1: Suitable for the variable torque load (load of draught fans, water pumps)of the
appointed parameters
F2.01
Motor rated power Factory Setting 0
Setting Range
0.47.5kW
F2.02
Motor rated frequency Factory Setting 50.00Hz
Setting Range
10.00HzF0.10
F2.03
Motor rated rotation
speed
Factory Setting Defined by inverter model
Setting Range
036000rpm
F2.04
Motor rated voltage Factory Setting Defined by inverter model
Setting Options
0480V
F2.05
Motor rated current Factory Setting
Different according to inverter
model
Setting Range
0.82000A
F2.06
Motor stator resistance Factory Setting Defined by inverter model
Setting Range
0.00165.53
F2.07
Motor rotator resistance Factory Setting Defined by inverter model
Setting Range
0.00165.53
Attention
Please set the parameters according to the nameplate of the electric motor.
To make sure the superior control performance of vector control, please set accurate
parameters, accurate parameter identification comes from the right settings of rated
parameters of the electric motor.
In order to ensure control performance, please configure the electric motor according to the
standards of electric motor adaption of the VFD. If the gap between motor power and the
standard adaptation motor is too large, the control performance of the VFD will decline
sharply.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SAJ 8000m Series and is the answer not in the manual?

SAJ 8000m Series Specifications

General IconGeneral
BrandSAJ
Model8000m Series
CategoryController
LanguageEnglish

Related product manuals